Avigilon Panel reset
EP1502/EP2500 Controller Setup Guide (kerisys.com)
You can't login to a panel unless S1 DIP 1 is "on"?
Before you can log into the controller using the default user name and password, you must:
- Transition S1 DIP switch 1 to the ON position (Do NOT cycle the power).
- You can then log in using the user name of admin and the password of password.
- Once logged in you should click on the Users link on the left.
- Add a new username and password then Apply the settings.
- Next time, if you login using the new log on credentials you will not need to adjust the S1 DIP switch.
Factory Default DIP Switch Setting
You have to configure the S1 DIP switch to set the controller to its factory default settings.
Switch
Definitions
1
2
3
4
OFF
OFF
X
OFF
Normal operating mode.
ON
X
X
X
After initialization, enable default User Name (admin) and Password (password). The switch is read on the fly, no need to re-boot. See Special Features for more information on configuration options available with Switch 1.
OFF
ON
ON
OFF
Use factory default communication parameters.(Address: 192.168.0.251 Port: 3001)
ON
ON
X
OFF
Use OEM default communication parameters. Enable “Bulk Erase” Option. See the Hardware Installation Manual for more information on “Bulk Erase.”
X
X
ON
X
Disable TLS secure link. Switch is read only when logging on.